Sewage Disposal Systems Regulations
This regulation requires licences for septic contractors, site assessors, installers, and pumpers, and sets filing, notice, design, installation, recordkeeping, disposal, and decommissioning rules for sewage disposal systems.
- Jurisdiction
- Canada — Prince Edward Island
- Instrument
- Regulation
- Version
- Undated source snapshot
- Language
- en
- Official source
- View official record ↗
Statute overview
About this statute
This regulation requires licences for septic contractors, site assessors, installers, and pumpers, and sets filing, notice, design, installation, recordkeeping, disposal, and decommissioning rules for sewage disposal systems. This segment sets technical rules for holding tanks, interceptors, grease chambers, fill, buffers, and disposal-field design. This provision sets minimum and table-based design wastewater flows, requires supporting flow data when submitted, and lets the Minister reduce flows or decide disputed flow rates.
Search within this statute
Search all stored provisions in this version.
Legal text
Provisions of Sewage Disposal Systems Regulations
Showing 3 of 3
Part document.segment-1
Sewage Disposal Systems Regulations — segment 1
- document.segment-1 Verify source ↗
Sewage Disposal Systems Regulations — segment 1
This regulation requires licences for septic contractors, site assessors, installers, and pumpers, and sets filing, notice, design, installation, recordkeeping, disposal, and decommissioning rules for sewage disposal systems.
t WATER ACT SEWAGE DISPOSAL SYSTEMS REGULATIONS PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to March 30, 2024. It is intended for information and reference purposes only. This document is not the official version of these regulations. The regulations and the amendments printed in the Royal Gazette should be consulted on the Prince Edward Island Government web site to determine the authoritative text of these regulations. For more information concerning the history of these regulations, please see the Table of Regulations on the Prince Edward Island Government web site (www.princeedwardisland.ca). If you find any errors or omissions in this consolidation, please contact: Legislative Counsel Office Tel: (902) 368-4292 Email: legislation@gov.pe.ca Sewage Disposal Systems Regulations Table of Contents SEWAGE DISPOSAL SYSTEMS REGULATIONS Table of Contents Section Page INTERPRETATION 5 1. Interpretation ............................................................................................................................................ 5 2. Schedule ................................................................................................................................................... 6 LICENCES AND REGISTRATION 6 3. Septic contractor’s licence required ......................................................................................................... 6 4. Site assessor’s licence required ................................................................................................................ 7 5. Installer .................................................................................................................................................... 7 6. Pumper’s licence required ........................................................................................................................ 7 SITE ASSESSMENT AND SYSTEM DESIGN 8 7. System flow 6,810 litres per day or less................................................................................................... 8 8. System flow > 6,810 litres per day ........................................................................................................... 8 9. Site suitability assessment registration form ............................................................................................ 9 INSTALLATION, RECONSTRUCTION OR MODIFICATION 9 10. Installation of sewage disposal system ..................................................................................................... 9 11. Reconstruction or modification ................................................................................................................ 9 12. Order due to weather or ground conditions .............................................................................................. 9 13. Site supervision ...................................................................................................................................... 10 14. Certificate of compliance, septic contractor ........................................................................................... 10 CLEANING AND DISPOSAL 10 15. Records .................................................................................................................................................. 10 16. Holding of septage ................................................................................................................................. 11 DECOMMISSIONING 11 17. Abandoned septic tank ........................................................................................................................... 11 GENERAL 12 18. Former regulations ................................................................................................................................. 12 SECTION 1 STANDARDS FOR SELECTION OF ON-SITE SEWAGE DISPOSAL SYSTEMS 13 1.1 INTRODUCTION 13 1.1.1 Definitions.............................................................................................................................................. 13 1.2 BUILDING SEWERS 14 1.3 SEPTIC TANKS AND EFFLUENT LINES 15 1.3.1 Septic Tank Sizing ................................................................................................................................. 15 1.3.2 Effluent Line .......................................................................................................................................... 17 1.3.3 Gravity Effluent Line Requirements ...................................................................................................... 17 1.3.4 Pressure Effluent Line Requirements ..................................................................................................... 18 1.3.5 Pressurized System Pipe Requirements ................................................................................................. 19 c t Current to: March 30, 2024 Page 3 Table of Contents Sewage Disposal Systems Regulations 1.4 PUMP AND DOSING CHAMBERS 19 1.4.1 Dosing Systems ...................................................................................................................................... 20 1.4.2 Pumping Chamber Requirements & Sizing ............................................................................................ 21 1.4.3 Siphon Breaker ....................................................................................................................................... 21 1.4.4 Mechanical-Electrical System ................................................................................................................ 22 1.5 Holding Tanks (Figure 1.6) .................................................................................................................... 23 1.5.2 Riser and Lid .......................................................................................................................................... 26 1.6 INTERCEPTORS 26 1.6.1 Interceptor Trench .................................................................................................................................. 26 1.6.2 Interceptor Swale .................................................................................................................................... 29 1.7 GREASE CHAMBERS 29 1.8 FINAL COVER MATERIAL 30 1.9 PRODUCTS APPROVED BY MINISTER 31 1.10 DISPOSAL FIELDS SELECTION & LAYOUT 31 1.10.1 Introduction ............................................................................................................................................ 31 1.10.2 Disposal Field Sizing ............................................................................................................................. 32 1.10.3 Multiple Trench ...................................................................................................................................... 33 1.10.4 Alternative Multiple Trench ................................................................................................................... 35 1.10.5 Gravelless Disposal Systems ................................................................................................................. 36 1.10.7 Contour Trench C2 ................................................................................................................................ 43 1.10.8 Contour Trench C3 ................................................................................................................................ 46 1.11 GRAVELLESS DISPOSAL SYSTEM 49 1.12 REQUIREMENTS FOR GOOD QUALITY FILL (GQF) 50 1.12.1 Site Preparation ...................................................................................................................................... 50 1.12.2 Specifications ........................................................................................................................................ 50 1.12.3 Contractor’s Responsibility .................................................................................................................... 50 1.13 BUFFERS 51 Page 4 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 1 WATER ACT CHAPTER W-1.1 SEWAGE DISPOSAL SYSTEMS REGULATIONS Pursuant to section 76 of the Water Act R.S.P.E.I. 1988, Cap. W-1.1, Council made the following regulations: INTERPRETATION 1. Interpretation (1) In these regulations (a) “Act” means the Water Act R.S.P.E.I. 1988, Cap. W-1.1; (b) “engineer” means a person who is authorized to practise professional engineering under the Engineering Profession Act, R.S.P.E.I. 1988, Cap. E-8.1; (c) “holding tank” means a closed, water-tight receptacle that is designed and used to receive and store sewage or septic tank effluent and does not discharge waste water; (d) “installer” means a person who is registered as an installer and holds a certificate of registration under section 5; (e) “permeable soil” means soil having a hydraulic conductivity in the range of 8.0 x 10-3 cm/s to 8.0 x 10-5 cm/s (3.1 x 10-8 in/s to 3.1 x 10-5 in/s); (f) “pumper” means a person who holds a valid pumper’s licence; (g) “pumper’s licence” means a pumper’s licence issued under section 6; (h) “septage” means all settled solids, scum, liquid or other material removed from a septic tank or disposal field; (i) “septic contractor” means a person who holds a valid septic contractor’s licence; (j) “septic contractor’s licence” means a septic contractor’s licence issued under section 3; (k) “septic tank” means a watertight receptacle that receives sewage, which is designed and installed to permit settling of settleable solids from the sewage, retention of the solids and scum, partial digestion of the organic matter, and discharge of the liquid portion into a disposal field; (l) “sewage disposal system registration form” means a form referred to in subsection 9(2); (m) “site assessor” means a person who holds a valid site assessor’s licence; (n) “site assessor’s licence” means a licence issued under section 4; (o) “site suitability assessment” means an assessment completed on property to determine the suitability of that property for on-site sewage disposal; c t Current to: March 30, 2024 Page 5 Section 2 Sewage Disposal Systems Regulations (p) “site suitability assessment registration form” means the form referred to in subsection 9(1); (q) “unstabilized sewage” means sewage that has been held in a septic tank or holding tank for less than 30 days. Imperial measurements (2) In these regulations, Imperial measurements are added editorially for convenience and are not intended to be relied on as exact equivalents of the metric measurements specified. (EC504/21) 2. Schedule (1) The “Minimum Regulatory Requirements for the Selection and Construction of On-Site Sewage Disposal Systems on Prince Edward Island” set out in the Schedule to these regulations are hereby adopted and form part of these regulations. Responsibility of septic contractor (2) Unless stated otherwise in the regulations, a septic contractor is responsible for ensuring that the requirements of the Schedule are met in respect of a sewage disposal system installed, reconstructed or modified by the septic contractor. (EC504/21) LICENCES AND REGISTRATION 3. Septic contractor’s licence required (1) For the purpose of section 51 of the Act, a person may undertake the installation, reconstruction, modification or decommissioning of a sewage disposal system if the person holds a valid septic contractor’s licence. Issuance of licence (2) On receipt of an application in the form required by the Minister and the licence fee of $250, the Minister may issue a septic contractor’s licence to an applicant who (a) has attended a seminar approved by the Minister; (b) has completed and passed an examination administered by the Minister; and (c) holds (i) a site assessor’s licence, or (ii) a licence issued by another province or territory that the Minister considers to be substantially equivalent to a site assessor’s licence. Term of licence and renewal (3) A septic contractor’s licence expires on the date indicated on the licence, which shall not be more than two years from the date of issuance, and may be renewed on payment of the licence renewal fee of $250. Terms and conditions (4) Subject to subsection (5), the following terms and conditions apply to a septic contractor’s licence: (a) the septic contractor shall continuously hold a valid site assessor’s licence; (b) the septic contractor shall attend a seminar approved by the Minister at least once every two years. Page 6 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 4 Exception (5) Clauses (2)(c) and (4)(a) do not apply to a person who held a septic contractor’s licence but not a site assessor’s licence under the Environmental Protection Act Sewage Disposal Systems Regulations (EC625/13) immediately before the coming into force of these regulations. (EC504/21) 4. Site assessor’s licence required (1) No person, other than an engineer or environment officer, shall conduct a site suitability assessment unless the person holds a valid site assessor’s licence. Issuance of licence (2) On receipt of an application in the form required by the Minister and the licence fee of $250, the Minister may issue a site assessor’s licence to an applicant who (a) either (i) has completed at least two years of post-secondary education in a related field of study, or (ii) has practical experience in a related field that the Minister considers to be equivalent to the post-secondary education referred to in subclause (i); and (b) either (i) has successfully completed a course of instruction approved by the Minister, or (ii) holds a licence issued by another province or territory that the Minister considers to be substantially equivalent to a site assessor’s licence. Term of licence and renewal (3) A site assessor’s licence expires on the date indicated on the licence, which shall not be more than two years from the date of issuance, and may be renewed on payment of the licence renewal fee of $250. (EC504/21) 5. Installer (1) On receipt of an application in the form required by the Minister and the registration fee of $25, the Minister may register as an installer and issue a certificate of registration to an applicant who attends a seminar approved by the Minister. Term of registration and renewal (2) The registration of an installer expires on the date indicated on the certificate of registration, which shall not be more than two years from the date of issuance, and may be renewed on payment of the renewal fee of $25. Seminar (3) It is a term and condition on the registration of an installer that the installer shall attend a seminar approved by the Minister at least once every two years. (EC504/21) 6. Pumper’s licence required (1) No person shall undertake the cleaning of a sewage disposal system or the disposal of septage or unstabilized sewage unless the person holds a valid pumper’s licence. c t Current to: March 30, 2024 Page 7 Section 7 Sewage Disposal Systems Regulations Issuance of licence (2) On receipt of an application in the form required by the Minister and the licence fee of $250, the Minister may issue a pumper’s licence to the applicant. Term of licence and renewal (3) A pumper’s licence expires on the date indicated on the licence, which shall not be more than two years from the date of issuance, and may be renewed on payment of the licence renewal fee of $250. (EC504/21) SITE ASSESSMENT AND SYSTEM DESIGN 7. System flow 6,810 litres per day or less (1) This section applies where a sewage disposal system with a flow of 6,810 litres per day or less is required. Filing of site suitability assessment registration form (2) On completing the site suitability assessment, the engineer, environment officer or site assessor, as the case may be, shall complete a site suitability assessment registration form, file it with the Minister and pay the filing fee of $100. Filing of sewage disposal system registration form (3) The septic contractor shall (a) determine the specifications of the sewage disposal system in accordance with the Schedule; and (b) complete the sewage disposal system registration form, file it with the Minister and pay the filing fee of $100. Alteration of system specifications (4) Where the septic contractor alters the specifications of the sewage disposal system after filing the sewage disposal system registration form, the septic contractor shall notify the Minister, in writing, of the alterations. (EC504/21) 8. System flow > 6,810 litres per day (1) This section applies where a sewage disposal system with a flow greater than 6,810 litres per day is required. Engineer shall design (2) The sewage disposal system shall be designed by an engineer. Completion of site suitability assessment registration form (3) On completing the site suitability assessment, the engineer, environment officer or site assessor, as the case may be, shall complete a site suitability assessment registration form and provide it to the engineer responsible for designing the sewage disposal system. Filing of forms (4) The engineer responsible for designing the sewage disposal system shall (a) confirm the contents of the site suitability assessment registration form, file it with the Minister and pay the filing fee of $100; and Page 8 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 9 (b) complete a sewage disposal system registration form, file it and the design plan with the Minister, and pay the filing fee of $100. Alteration of design (5) Where the engineer alters the design of the sewage disposal system after filing the sewage disposal system registration form, the engineer shall notify the Minister, in writing, of the alterations. (EC504/21) 9. Site suitability assessment registration form (1) A site suitability assessment registration form shall be in the form approved by the Minister and contain the information required by the Minister, including (a) the lot category of the site determined in accordance with section 23 of the Planning Act Subdivision and Development Regulations (EC693/00); and (b) the depth of permeable soil on the site. Sewage disposal system registration form (2) A sewage disposal system registration form shall be in the form approved by the Minister and contain the information required by the Minister. (EC504/21) INSTALLATION, RECONSTRUCTION OR MODIFICATION 10. Installation of sewage disposal system A septic contractor shall not install a sewage disposal system unless (a) a site suitability assessment has been conducted in accordance with section 7 or 8; and (b) at least 24 hours before commencing the installation, (i) a site suitability assessment registration form and a sewage disposal system registration form have been filed in accordance with section 7 or 8, and (ii) the septic contractor has given notice of the installation to the Minister in the manner required by the Minister. (EC504/21) 11. Reconstruction or modification A septic contractor shall not reconstruct or modify a sewage disposal system unless, at least 24 hours before commencing the reconstruction or modification, the septic contractor (a) completes a sewage disposal system registration form, files it with the Minister and pays the filing fee of $100; and (b) gives notice of the reconstruction or modification to the Minister in the manner required by the Minister. (EC504/21) 12. Order due to weather or ground conditions (1) The Minister may, by order, prohibit the installation, reconstruction or modification of a sewage disposal system when, in the Minister’s opinion, weather conditions or ground conditions are unsuitable. c t Current to: March 30, 2024 Page 9 Section 13 Sewage Disposal Systems Regulations Order re system modification (2) Where a sewage disposal system is to be modified, the Minister may, by order, for the purpose of protecting public health or the environment, require the entire sewage disposal system or any part of it to be reconstructed or modified. Order to uncover system for inspection (3) Where a septic contractor fails to provide the required notice under section 10 or 11 and the sewage disposal system has been covered following installation, reconstruction or modification, the Minister may, by order, require the person responsible in respect of the site, an engineer or the septic contractor to uncover all or part of the system for inspection. (EC504/21) 13. Site supervision A septic contractor shall ensure that the septic contractor or an installer who is employed by the septic contractor is present on site during the installation, reconstruction or modification of a sewage disposal system. (EC504/21) 14. Certificate of compliance, septic contractor (1) Within 60 days of installing a sewage disposal system with a flow of 6,810 litres per day or less, or reconstructing or modifying a sewage disposal system, a septic contractor shall provide to the person responsible in respect of the site and the Minister, a certificate of compliance in the form required by the Minister certifying that the sewage disposal system has been installed, reconstructed or modified in accordance with the sewage disposal system registration form and these regulations. Certificate of compliance, engineer (2) Within 60 days of the installation of a sewage disposal system with a flow greater than 6,810 litres per day, the engineer responsible for designing the system shall provide to the person responsible in respect of the site and the Minister, a certificate of compliance in the form required by the Minister certifying that the sewage disposal system has been installed in accordance with the sewage disposal system registration form and design plan. (EC504/21) CLEANING AND DISPOSAL 15. Records (1) A pumper shall, in respect of each sewage disposal system from which the pumper has removed septage, create and maintain a record in the form approved by the Minister containing the following information: (a) the civic address where the sewage disposal system is located; (b) the date on which septage was removed; (c) the volume of septage removed on that date; (d) the date and location of the disposal of the septage. Entry of information (2) A pumper shall enter the information required under subsection (1) in the record for a sewage disposal system immediately after removing septage. Page 10 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 16 Annual report (3) A pumper shall, in respect of the sewage disposal systems from which the pumper has removed septage in a calendar year, submit a written report to the Minister, on or before April 1 of the next calendar year, in the form approved by the Minister, containing the following information in respect of each sewage disposal system: (a) the civic address where the sewage disposal system is located; (b) the dates on which septage was removed; (c) the total annual volume of septage removed; (d) the dates and locations of disposal of the septage. Duties respecting records (4) A pumper shall, in respect of a record created under this section, (a) retain the record for a period of three years from the date on which the septage was removed from the sewage disposal system; and (b) make the record available immediately, on request, to an environment officer. (EC504/21) 16. Holding of septage (1) A pumper shall not place septage in a holding site without the prior approval of the Minister. Disposal of unstabilized sewage or septage (2) A pumper shall not dispose of unstabilized sewage or septage except through a wastewater treatment system approved by the Minister. (EC504/21) DECOMMISSIONING 17. Abandoned septic tank (1) For the purposes of this section, a sewage disposal system is abandoned if it is disconnected from all sources of sewage on the property served by the sewage disposal system. Duty of person responsible for property (2) The person responsible for a property served by a sewage disposal system that has been abandoned shall ensure that the sewage disposal system is decommissioned, in accordance with this section, by a septic contractor within 30 days after the sewage disposal system is abandoned. Decommissioning (3) A septic contractor shall decommission an abandoned sewage disposal system by (a) removing the contents of the septic tank, disinfecting the septic tank and filling the septic tank with clean soil fill; or (b) removing the septic tank, disinfecting the resulting excavation and filling the excavation with clean soil fill. Notification to Minister (4) Where a septic contractor decommissions an abandoned sewage disposal system, the septic contractor shall notify the Minister in writing within 60 days of the decommissioning. (EC504/21) c t Current to: March 30, 2024 Page 11 Section 18 Sewage Disposal Systems Regulations GENERAL 18. Former regulations On and after the commencement of these regulations, a reference in an enactment to the Environmental Protection Act Sewage Disposal Systems Regulations (EC625/13) is deemed to be a reference to these regulations. (EC504/21) Page 12 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 SCHEDULE Minimum Regulatory Requirements for On-Site Sewage Disposal Systems on Prince Edward Island Appendix ‘A’ Section 1 Standards for Selection of On-Site Sewage Disposal Systems 1.1 Introduction The specifications for a sewage disposal system with a flow of up to 2,270 L/day, for a residential unit with up to five bedrooms, can be selected from Table 1.1 and selection tables in Appendix D (Disposal Field Length Selection Table) once the soils of the area have been categorized. Septic tank and disposal field sizing requirements for a sewage disposal system with a flow from 2,271 L/day up to 6,810L/day can be determined using the Design Flow Table (Appendix B) and the Disposal Field Length Selection Table (Appendix D). Sewage disposal systems with a flow rate greater than 6,810 L/day (1,500 Igal/day) shall be assessed and designed by an engineer. 1.1.1 Definitions alternative multiple trench disposal field - means a multiple trench disposal field oriented across the slope of a property with lateral spacing of no less than 4 metres (13 ft) between the lines; ANSI – means the American National Standards Institute; barrier material - means a light weight (50 g/m2 or more) nonwoven (i.e. felted, needle punched or heat bonded fibre) fabric or proprietary geotextile with a permeability greater than 0.001 m/s (0.04 in/sec) and an opening size of less than 700 μm (0.028 in); bedrock – means a solid or continuous body of rock, with or without fractures, or a weathered or broken body or rock fragments overlying a solid body of rock; capacity - means the liquid capacity of a septic tank between the waterline and the floor of the tank; Category I, II, III, IV or V – means the lot category determined in accordance with the Subdivision and Planning Act Regulations made under the Planning Act; certified – means guaranteed by a Standards Council of Canada Accredited Testing Agency as being in conformance with the latest CSA Standard pertinent to the application of the product; contour trench disposal field - means a relatively narrow and shallow disposal bed constructed in a trench of constant depth, with both the trench bottom and the lip of the trench wall at the ground surface horizontal throughout the entire length (see Sections 1.10.6 –1.10.8); CSA – means the Canadian Standards Association; disposal field - means that part of an on-site sewage disposal system designed and installed in accordance with these regulations for the subsurface distribution of septic tank effluent into the soil; drainage pipe - means the certified, perforated, rigid, straight, sewer pipe used in a disposal field; c t Current to: March 30, 2024 Page 13 Section 18 Sewage Disposal Systems Regulations dwelling - means a building or portion thereof designed, arranged or intended for residential occupancy; dwelling unit – means two or more rooms used or intended for domestic use of one or more individuals living as a single housekeeping unit with cooking and sanitary facilities; effluent - means sewage after it has passed through a septic tank or some other type of treatment; effluent line - means a pipe that transports effluent from a septic tank to a disposal field; existing parcel - means any parcel in existence prior to June 12, 1993; filter sand - means clean, washed, screened or natural sand having less than 10% by weight retained on a 10 mm (3/8 in) sieve and less than 2% by weight passing a 0.075 mm (#200 US std.) sieve and the permeability of the sand must be not less than 0.0004 m/s (0.0013 ft/s); good quality fill – means fill composed of a reasonably uniform sand or sandy gravel and possibly a small proportion of silt/clay where no more than 30 % of the material shall be retained on a 10 mm (3/8 in) sieve and a minimum of 2.5 % and a maximum of 15% passing the 0.075 mm sieve (#200 US std.); gravel - means clean, washed or screened small pieces of rock or crushed rock of a consistency or hardness which is not conducive to premature deterioration, and of which 98% by weight shall pass a 40 mm (1½ in) screen and 98% by weight shall be retained on a 12.5 mm (½ in) screen; grease interceptor tank - means a tank installed in front of the septic tank to remove grease, oil and fats from sewage; header - means pipe used to connect the ends of lines of drainage pipe or leaching chambers; leaching chamber - means a prefabricated device approved by the authority having jurisdiction for use in a disposal field as an alternative to gravel and drainage pipe; leaching chamber disposal field - means a system of leaching chambers arranged in a multiple trench configuration (see Section 1.10.5); liquid depth - means the maximum vertical depth of liquid which a septic tank can contain before the liquid discharges through the septic tank outlet; multiple family dwelling - means a building containing three or more dwelling units; multiple trench disposal field - means a system of drainage pipes and gravel arranged in the form of narrow, parallel trenches connected to a header (see Section 1.10.3); NSF – means the National Sanitation Foundation; natural boundary – means the visible high water mark of any stream, river or other body of water; permeable soil (natural) - means soil having a hydraulic conductivity in the range of 8.0 x 10-3 cm/s to 8.0 x 10-5 cm/s (3.1 x 10-8 in/s to 3.1 x 10-5 in/s); pressure distribution system - means a distribution system designed such that a pump or siphon supplies septic tank effluent to non- perforated pipe that is drilled with holes of such diameter and spacing that the top header, full length of all interconnecting pipes, and the bottom header are under a positive pressure; sewer line - means a pipe that transports sewage from a building to a septic tank or a sewer collection main; standard disposal field - means a multiple trench or alternative multiple trench disposal field; top header - means the first header of each disposal field to receive effluent from the septic tank (see Figure 1.9); waterline - means the maximum elevation of the liquid in a septic tank; water table - means the level at which water stands in a shallow well open along its depth and penetrating the surficial deposits just deeply enough to encounter standing water in the bottom (level of water in saturated soil where hydraulic pressure is equal to zero). 1.2 Building Sewers A building sewer for a single unit dwelling is defined as the part of the building drainage system carrying sewage that extends from the septic tank or public sewer to a point 900 mm to 1500 mm out from the foundation wall. The building sewer shall be installed with the following conditions: 1. Minimum 100 mm diameter pipe, non-perforated, rigid, smooth bore, watertight joints with gaskets or solvent welded, DR35, certified to CAN/CSA B182.1:21 and B182.2:21 standards. 2. Laid straight on a grade not less than two per cent. Page 14 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 3. If a change in direction is needed the fittings shall consist of certified, long sweep fittings. The use of these fittings should be limited. 4. Located a minimum 0.5 metres from any potable water service line. 5. Located a minimum of 3.0 metres from a domestic water well. 6. Cleanouts extended to the ground surface shall be provided at intervals of not more than 30 m, if the length of the building sewer exceeds 60 m or any direction change greater than 90 degrees. 7. Install pipe and fittings according to manufacturer’s recommendations. 1.3 Septic Tanks and Effluent Lines The following requirements shall apply to any tank that is selected or designed for use as a septic tank, with respect to construction standards, selection criteria and setback requirements: 1. The septic tank shall be designed to carry a minimum of 600 mm of earth cover. 2. All materials shall be installed according to the manufacturer’s recommendations. These recommendations shall be submitted to the Minister by the manufacturer. 3. The manufacturer of a prefabricated tank shall provide to the installer instructions for assembly and installation of the tank. These instructions shall detail the entire installation process to ensure that the tank is watertight. These instructions shall include, but not limited to, the preparation of excavation, installation of tank, backfilling of tank, connection detail of inlet/outlet piping, etc. 4. The instructions shall be submitted to the Minister for review to assure that they address the requirements of these Standards. 5. Concrete septic tanks shall be constructed to conform to CAN/CSA B66:21 standards. Polyethylene and fiberglass septic tanks shall be certified to CAN/CSA B66:21 standards. 6. All septic tanks shall be watertight. 7. All septic tanks shall have risers installed as outlined in the appropriate sections. As a minimum an access riser shall be installed over the outlet and in each chamber, if the tank has multiple chambers. 8. Where a tank is installed in an area where high groundwater levels may occur, the manufacturer shall include instructions to prevent flotation of the tank. 9. A sectional pre-fabricated tank may be assembled on site, provided that the manufacturer's instructions are followed to produce a watertight tank. 10. Where a tank is manufactured from concrete, the bung hole must be sealed in a watertight manner. 11. The tank shall be tested for water tightness on site after assembly. 12. All septic tanks shall be installed in accordance with the separation distances outlined in Appendix C, Table C1. 13. All septic tanks shall be equipped with a tamper resistant lid labeled “DANGER – DO NOT ENTER”. 14. All septic tanks shall be equipped with an effluent filter certified to NSF/ANSI 46-2014 standards. 15. A septic tank manufactured on-site shall be designed by an engineer and conform to applicable CSA Standards. 1.3.1 Septic Tank Sizing Any septic tank is required to meet the following sizing requirements: (Figure 1.1 - Septic Tank) 1. Septic tanks for dwellings must have a capacity not less than that stated in Table 1.1. 2. For larger systems the minimum capacity shall be calculated as follows: For peak average daily flows up to 6810 L/day: c t Current to: March 30, 2024 Page 15 Section 18 Sewage Disposal Systems Regulations Tank Volume(TV) = 2 x Q Where: Q – peak average daily flow in litres (L/day) TV– liquid volume of septic tank in litres (L) The minimum required septic tank size is 3,400 L. Septic tank sizes larger than the required minimum may reduce problems and extend the life of an on-site system. Septic tank capacity shall be increased by 25 per cent where a garbage grinder is used. Access to a tank shall be provided over the inlet and outlet for easier service. The dimension of any opening shall meet latest CSA standards. All septic tanks shall be fitted with a riser located at the outlet of the septic tank. All outlets of septic tanks shall be equipped with an effluent filter (Figure 1.2) sized to manufacturer’s recommendations. The septic tank shall be installed according to the manufacture’s recommendations. Two compartment tanks are required when the daily flow exceeds 4,100 L to reduce solids carry-over to the disposal field. Each compartment shall have an access riser for purpose of maintenance that extends to the ground surface as outlined in the riser section. The interconnecting port in the divider should be located approximately one-half way in the liquid depth. The final compartment should be approximately one-third of the total volume. Page 16 Current to: March 30, 2024 t c Figure 1.1 Septic Tank Sewage Disposal Systems Regulations Section 18 Table 1.1 Minimum Capacity of Septic Tanks for Dwellings Number of Bedrooms Minimum Liquid Capacity in litres Up to 3 3,400 4 4,090 5 4,500 When selecting a tank, the depth of bury must be considered. If it is greater than 600 mm, the tank should be stamped to indicate that it has been designed to withstand burial to the required depth. 1.3.2 Effluent Line The effluent line, which is the pipe that allows effluent to move from the septic tank to the distribution field, can be fed by a gravity distribution system or a pressure distribution system. The following are the requirements of each: 1.3.3 Gravity Effluent Line Requirements 1. A gravity line shall be a PVC DR35 100 mm pipe, solvent welded or gasket, non-perforated, rigid, smooth bore and watertight, and shall be certified to CAN/CSA B182.1:21 and B182.2:21 standards. 2. A gravity line shall have watertight joints. 3. A gravity line shall have a grade not less than one per cent. c t Current to: March 30, 2024 Page 17 Section 18 Sewage Disposal Systems Regulations Figure 1.2 Effluent Filter 1.3.4 Pressure Effluent Line Requirements 1. Pressure line shall be a 38 mm minimum (1.5 inch) diameter pipe, non-perforated, rigid, smooth bore, watertight, PVC SDR 26, and shall be certified to CSA B137-2013 standards. 2. The joints of the pressure pipe shall be watertight and installed according to the manufacturer’s recommendations. 3. Provide appropriate freezing protection methods such as adequate depth of cover, insulation and/or draining of effluent lines after each pump cycle stops. 4. Pressure line to the tank (if necessary) shall be a minimum of 3 metres from a domestic water well. Page 18 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 1.3.5 Pressurized System Pipe Requirements A pressurized system is more effective than a gravity system as it provides both uniform distribution and periodic dosing of the disposal field. The disadvantage of a pressurized system is the higher capital cost and the extra maintenance requirements associated with the pump or dosing chamber. Pressurizing using a pump or dosing chamber is required: • where an end fed disposal line is longer than 30.5 linear metres • where the one disposal bed exceeds 152.4 linear metres • where the natural ground slope is not uniform and a gravity system might concentrate effluent at one on more weak spots in the field • for any system where the disposal field is at a higher elevation than the septic tank Where a pump or dosing chamber is required, the solid pipe from the pump or dosing chamber to the disposal field must have a minimum diameter as specified by the pump or siphon manufacturer but shall not be less than 38 mm. Piping within the dosing chamber and extending 1 metre from chamber shall be schedule 40, certified to CSA B137 Series 2013 standards. All pumped systems shall be connected to the disposal field using a “siphon breaker” as shown in Figure 1.4. For any system selected to serve a single family home using a pump or dosing chamber, the perforated pipe in the distribution field can be similar to gravity distribution pipe (Subsection 1.3.4) with only a 13 mm hole drilled in the top of the pipe 100 mm from the end cap(s). In addition the distribution piping must be placed such that there is no slope on the piping in the disposal trench. For systems serving more than 6810 L/day (designed by an engineer), the pipe diameter, and hole spacing must be calculated, based on the system hydraulics, in an effort to provide uniform distribution throughout the disposal field. Maintain a minimum 600 mm of head at the most distant orifice. In a designed system the minimum acceptable pipe diameter is 38 mm. The design shall allow for distribution pipe to drain after the completion of each dose. 1.4 Pump and Dosing Chambers The pump or dosing chamber discharge capacity must be sized to distribute effluent over the entire disposal field during each dose. This allows utilization of the entire field and minimizes the possibility of breakout of effluent in a localized area. Periodic dosing also allows the infiltrative surface to drain between doses. These cycles of alternate dosing and resting may maintain higher infiltration rates in the clogging mat and thus extend the life of the system. c t Current to: March 30, 2024 Page 19 Section 18 Sewage Disposal Systems Regulations Figure 1.3 Pumping Installation Where a dosing system is used the minimum dosing frequency is at least two times per day. When a large system is designed, other dosing frequencies may be necessary. The discharge volume must be large enough to flood the entire distribution pipe. Unless the Septic Contractor or Engineer specifically selects the pump to be used, it is the installer’s responsibility to ensure that the pump has the proper capacity of achieving equal distribution throughout the field. 1.4.1 Dosing Systems There are two types of dosing systems: High Pressure Systems provide a calculated residual head (squirt height) throughout the entire distribution network within the disposal field. The piping network continues throughout the entire disposal field and is typically 50 mm in diameter depending upon system type, hydraulics and manufacturer’s recommendations. This pipe can be laid on the gravel bed or adequately suspended in a chamber system. These systems shall be designed by an engineer. Low Pressure Systems (Figure 1.4) provide pressure typically through a 50 mm force main (SDR 26 or equivalent) to a point whereby the pipe diameter size is increased to 100 mm. At this point the flow from the pump converts to gravity flow. Typically, the method to convert the high pressure flow to low pressure flow is at the entrance to the disposal header of the system. The 50 mm pressure line is connected to the header at the centre of the header. At this point the diameter of the line changes to 100 mm. This type of pressure installation is more common in residential and smaller commercial installations. When used in conjunction with a chamber system energy dissipation device such as a patio stone should be used at the entrance to each disposal line. Care is required when selecting the pump system to ensure that there is adequate total hydraulic head to overcome the system head (vertical distance between the lowest liquid elevation in the pump tank and the highest point within the system and any friction losses of the pipe, fittings, valves, etc.) Page 20 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 1.4.2 Pumping Chamber Requirements & Sizing A typical pump chamber is shown in Figure 1.3. Concrete tanks shall conform to CAN/CSA B66:21 standards. Polyethylene and fiberglass tanks shall be certified to CAN/CSA B66:21 standards. Reinforced concrete manholes shall conform to ASTM C478M standards and shall have a minimum diameter of 760 mm. Requirements for a pump chamber include the following: 1. The chamber shall be equipped with an audible and visible high level alarm, level controls, and other accessories required to assure effective and reliable operation. 2. A riser access shall be installed over the pump(s) for maintenance purposes. 3. The dimension of any opening shall meet CSA requirements and allow easy repair of pumping system. 4. All pumps shall be accessible and set to permit maintenance of pumping system without entering the pumping station. 5. The pump system shall accommodate the automatic start, stop and alarming of system based on the water level of the pump tank. 6. The pump system shall alternate pumps in a multiple pump system. 7. The elevation of the tank shall be such that any horizontal seam is located above the highest seasonal groundwater table or as recommended by the manufacturer. 8. The high water alarm level must be below the level of the horizontal seam. It is recommended that the pump chamber should be tested on site after assembly, for water tightness, proper operation and dosing quantities. The actual design of a pressure distribution system is based upon hydraulic principles and is beyond the scope of these Standards. In an attempt to simplify selection and standardize equipment requirements for single family homes, the required dosing capacity for siphons and pumps is as shown in Table 1.2. Table 1.2 Dosing Chambers and Pumps/Siphons - Capacity Flow Dosing Amount per Discharge Event in Litres Minimum Pump Chamber Capacity* 1000 L 500 L 1000 L 1350 L 675 L 1350 L 1500 L 750 L 1500 L * below any horizontal seam When pumping a considerable distance, the dosing amount and chamber size may have to be increased to compensate for effluent in the pump line returning to the pump chamber after the pump shuts off. 1.4.3 Siphon Breaker This section specifically addresses pressurized systems for delivery of septic tank effluent to a distribution system in a disposal field. When pumping down slope, the connection is to be made directly into the distribution pipe. If pumping upslope, a siphon breaker is required. The siphon breaker should be located where the pipe from the tank enters the distribution pipe. As well, one 13 mm hole should be placed 150 mm in from each end of the distribution pipe on the top of the pipe (Figure 1.5). c t Current to: March 30, 2024 Page 21 Section 18 Sewage Disposal Systems Regulations 1.4.4 Mechanical-Electrical System The complete electrical and mechanical systemCincluding pumps, controls, and switchesCmust be capable of functioning effectively, reliably, and for many years, in a corrosive environment. These systems shall be installed according to the Canadian Electrical Code Requirements. Page 22 Current to: March 30, 2024 t c Figure 1.4 Low Pressure Dosing System Sewage Disposal Systems Regulations Section 18 Figure 1.5 Distribution Pipes 1.5 Holding Tanks (Figure 1.6) Once the tank is full the material must be pumped out of the holding tank(s) by a Pumper and transported to a Wastewater Treatment Plant for final treatment. Typically, the frequency of the pump out is 5 to 7 days. The operating costs for this type of system can be expensive depending on water use. Water usage can be reduced with the installation of low flow fixtures such as six (6) litre toilets and low flow shower heads. This option should be carefully reviewed prior to installation so that the owner is fully aware of the ongoing operating cost. c t Current to: March 30, 2024 Page 23 Section 18 Sewage Disposal Systems Regulations Although the design and installation of a holding tank is similar to that of a septic tank, several additional considerations do exist and are outlined in Table 1.3.
Part document.segment-2
Sewage Disposal Systems Regulations — segment 2
- document.segment-2 Verify source ↗
Sewage Disposal Systems Regulations — segment 2
This segment sets technical rules for holding tanks, interceptors, grease chambers, fill, buffers, and disposal-field design.
Table 1.3 Holding Tank Considerations Holding Tank Considerations Minimum Size (Residential) 4,540 L Minimum Size (Commercial) 6,810 L or 2 days storage, whichever is greater Discharge No surface discharge allowed Alarm System Positioned to allow for ½ day storage after activation Accessibility Must be readily accessible to pumping vehicle Location Surface water diverted from tank area Water Use Water use should be reduced. The incremental costs of a large tank are minor compared to the cost of pumping over a long period of time. A small sized tank will require more frequent pumping and higher costs whereas a larger tank will require less pumping trips resulting in a lower cost in the long term. Maintenance and operating costs are substantially higher than operation of a regular sewage disposal system. The homeowner must understand that these costs are very high and that such costs may not be sustainable. Therefore, due to the costs, the use of a holding tank is only recommended as a last resort for on-site sewage treatment. The installation of a holding tank is an option for servicing given that one of the following conditions exists: a. in the opinion of the Minister, no practical alternative for the construction of a disposal field exists; b. the sewage holding tank is to be installed for commercial use and, in the opinion of the Minister there is no practical alternative for the installation of a disposal field. A septic contractor shall install a holding tank that complies with the manufacturer’s recommendations and these Standards. Page 24 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Figure 1.6 Holding Tank 1.5.1 Requirements for a Holding Tank 1. The requirements for a holding tank (Figure 1.6) are as follows: a. Volume is calculated as having twice the maximum expected daily flow as calculated in Appendix B. b. Minimum capacity of 4,540 L for residential use and 6,810 L for commercial use. c. Equipped with an audible and visible high level positioned so that it alarms at ¾ mark of the liquid capacity of the holding tank. d. Be readily accessible to a pumping truck. e. Be equipped with a riser over the inlet of the holding tank. f. Where a tank is installed in an area where high groundwater levels may occur, the manufacturer shall include instructions to prevent flotation of the tank. 2. The holding tank shall be installed according to the manufacture’s recommendations. 3. The proposal for a holding tank should include estimated yearly pump out costs from a Pumper. 4. A below ground tank shall be constructed of a non-metallic material. 5. A holding tank may be utilized for above ground services for an industrial/commercial operation, with the following requirements: c t Current to: March 30, 2024 Page 25 Section 18 Sewage Disposal Systems Regulations a. the tank shall be constructed of non-corrodible material; b. secondary containment shall be supplied (dykes, berms, etc); c. adequate weatherproofing shall be provided to prevent freezing in the tank or lines; d. the tank shall be supplied with adequate hold down and support systems; e. the inlet shall be on the top of the tank and the inlet line shall be self-draining; f. drain valves shall be locked when not in service or security in the form of a fence is provided; g. the tank vent shall be equipped with an odor control device or is extended sufficiently above grade to eliminate odors at ground level; h. the tank shall be installed in accordance with these Standards and the regulations. 6. Holding tanks shall be tested on site after assembly for water tightness. 7. Concrete holding tanks shall be constructed to conform to CSA B66:21 standards. Polyethylene and fiberglass tanks shall be certified to CSA B66:21 standards. 1.5.2 Riser and Lid 1. A single compartment septic, holding or pump tank shall have a riser section that a. is installed over the outlet opening of the top of the septic tank b. has a watertight seal where it joins the tank c. raises the outlet opening sufficiently to prevent flooding by surface water d. is equipped with a secure tamper resistant locking mechanism with lid e. lid to the riser provides watertight connection f. is labeled clearly “DANGER – DO NOT ENTER” g. all access openings (which are meant to be removed) over chambers with an opening greater than 200 mm in diameter, where there is a risk of accidental entry, shall have a secondary safety device that can withstand 91 kg of dead load. This device shall be easily and safely removable for inspection and maintenance once the lid has been removed. 2. A multiple compartment septic, holding or pump tank shall maintain the above requirements and shall have a minimum of one riser section located over each compartment. 3. Refer to Figure 1.6 for construction details 4. All riser and lid sections shall be installed according to the manufacturer’s recommendations. 5. Riser installation procedures shall be submitted by the manufacturer of the septic, holding or pump tanks. 1.6 Interceptors Interceptors are installed to intercept and divert surface water and groundwater upslope of a disposal field. An interceptor may be a trench filled with gravel, and containing a perforated pipe, or a swale (shallow trench) at the ground surface ( 1.7). Situations in which interceptors are required, and their locations relative to the ground surface, are defined in this Section. 1.6.1 Interceptor Trench An interceptor trench may be required or considered in order to address the following situations: (1) intercept and divert perched groundwater over a layer of impermeable soil; Page 26 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 (2) lower a seasonally high groundwater table upslope of a system that is located at lower end of a long slope; (3) intercept and divert surface water. In situation (1) the base of the trench should be set at least 150 mm into any impermeable layer. In situation (2) the depth of the trench should be a minimum of 150 mm below the bottom of the distribution field. In some cases this could result in an interceptor depth of up to 2 meters or more. In situation (3) a trench intended to intercept groundwater may also intercept surface water, or a trench (french drain) may be intended specifically to intercept and divert surface water. In the latter case the trench should be at least 300 mm deep. The interceptor trench should be 0.3 to 0.6 m in width and be filled with gravel. It may contain a perforated pipe with a slope. The trench must be sloped and sod placed where it is practical. Any interceptor trench must be long enough to divert the intercepted water to a point where it will not enter the disposal system and to where it will freely discharge to the surface, well down slope of the disposal field. It is recommended that the discharge point for the interceptor extend a minimum of 6 metres down slope of the disposal field or buffer. It is recommended that interceptors be located 5 to 10 metres upslope of the distribution field and that they pass no closer than within 5 metres of the end of the disposal field. If these separation distances cannot be achieved, it may be necessary to use impervious fill, such as compacted clay or bentonite, to ensure that surface/ground water does not enter the disposal field or have sewage enter the interceptor. If the trench is to intercept surface water either the gravel should be carried to within 50 mm of the surface (with no final cover material or sod) to allow surface water to enter the trench, or a swale should be included at the surface. The option of no final cover material may not be practical if there is a danger that sediment from upslope sources may clog the surface of the gravel. c t Current to: March 30, 2024 Page 27 Section 18 Sewage Disposal Systems Regulations Page 28 Current to: March 30, 2024 t c 1.7 Figure 1.7 Interceptor Trench and Swale Normally, the interceptor will drain past either or both ends of the disposal pipe, but for very long contour systems, an interceptor trench may be required to cross the disposal system at intervals. Where this crossing occurs the trench shall be constructed of solid pipe and should be laid a minimum of 500 mm below the bottom of the distribution trench ( 1.7). This drain line must be sealed with impermeable fill such as compacted clay or bentonite, for a minimum of 3 metres upslope and 5 metres down slope of the distribution field. Roof water must not be connected to the perforated pipe in an interceptor trench, but may be carried in a solid pipe in the same trench. Sewage Disposal Systems Regulations Section 18 In some cases such as highly permeable soils or high surface water flow, it may be advisable to place a liner on the down slope and bottom of the interceptor trench. If a liner is utilized, it must be placed along the bottom of the interceptor trench and up the vertical face of the down slope side of the trench; it must not to be placed on the upslope side of the trench ( 1.7). The liner shall be a 20 mil HDPE geomembrane with all seams over lapped a minimum of 0.5 metres with an appropriate sealant between the overlap. 1.6.2 Interceptor Swale A swale is intended to intercept surface water. It may be constructed alone, or at the surface of an interceptor trench. A swale should be at least 0.3 m deep and 0.6 m wide, and sodded with sloping sides to permit mowing. The length of any swale must be enough to divert the intercepted water to a point where it will not enter the disposal system and be sloped down and beyond the system. 1.7 Grease Chambers Grease chambers usually are not necessary on kitchen waste lines from residential development. However, in some commercial/institutional applications such as restaurants, school cafeterias and kitchens at summer camps, grease chambers are required. For the purpose of these Standards, a grease chamber is a chamber where grease floats to the surface while the cleaner water underneath is discharged to the septic tank. If this grease is not removed prior to entering the septic tank, large quantities may accumulate in the sewer and may block the building sewer or the effluent line to the disposal field, or the disposal field itself. The small grease traps found on some commercial/institutional kitchen drains are not considered adequate to protect the disposal system. The liquid volume of the grease chamber must be large enough to permit the water to cool allowing the grease to separate and rise to the top of the grease tank. The volume of a grease chamber shall be calculated using the following equation: For Restaurants: V = D * (HR/2) * GL * ST * LF grease Where: D - number of seats in dining area HR - number of hours open per day GL - gallons of wastewater per meal (2 or more) ST - Storage capacity (normally 2) LF - Loading factor depending on restaurant location 1.25 - central locations 1.0 - recreation areas 0.5 to 0.8 - other locations For Cafeterias or Institutional kitchens: V = M * GL * ST * LF grease c t Current to: March 30, 2024 Page 29 Section 18 Sewage Disposal Systems Regulations Where: M - Total number of meals served per day GL - Gallons of wastewater per meal (2 or more) ST - Storage capacity (normally 2) LF - Loading factor 1.0 with dishwasher 0.5 without dishwasher For all but large establishments, a converted 2,725 litre septic tank would have adequate capacity to serve as a grease chamber and may be the most economical solution even if it has more than the minimum required capacity. To convert a septic tank to a grease chamber, a tee can be installed on the outlet and extended to be 300 mm above the tank bottom ( Figure 1.8). To allow for proper maintenance, clean out covers shall be extended to finished grade. The cover shall be watertight and secured to prevent unauthorized entry. To minimize problems with grease solidifying in the sewer line the chamber should be located close to the building but not closer than 1.5 m, no more than 10 m from the fixture being served, and on undisturbed earth or compacted fill material.. 1.8 Final Cover Material The complete on-site sewage disposal system shall be covered with a layer of soils that will promote the growth of vegetation over the system. The material used to cover on-site sewage disposal systems is referred to as final cover material and will consist of: AImported, manufactured or site prepared material consisting of friable sandy silt or silty sand with a 4 to 25% organic matter content. The material must be free of debris, vegetation, and roots, with no stones greater than 25 mm in size. The material used shall be capable of supporting grass or similar vegetation. Page 30 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 c t Current to: March 30, 2024 Page 31 Figure 1.8 Grease Chamber 1.9 Products Approved by Minister The use of products or materials other than those described in these Standards may be considered by the Minister. In these cases, such a product or material must be used in accordance with the Minister’s approval recognizing it as a product for use in an on-site sewage disposal system. 1.10 Disposal Fields Selection & Layout 1.10.1 Introduction Most or all septic tank effluent will eventually reach the ground water table, directly or by travel in bedrock or very permeable soils. If the effluent is not adequately treated, drinking water and surface water may become contaminated. It is therefore required that there is well draining soil underneath the disposal field to ensure effluent is treated prior to recharging ground water. The roles of the disposal fields are to uniformly distribute the effluent into the soil profile below the system ensuring that the hydraulic capacity of the soil is not exceeded, and to provide treatment of the effluent leaving the system. This treatment will ensure the protection of groundwater and surface water resulting in the protection of public health and the environment. For the usual circumstances when a system is to be installed on a Category I, II or III lot the Regulations require a minimum of 600 mm of separation between the bottom of the trench and bedrock, maximum water table or soil with unacceptably high permeability. Please note: For systems installed on a Category IV lot, the reader is referred to the depths prescribed in Appendix D, (Category IV) and not those shown in this section or some of the sketches in the document. The separation distance under the system can be achieved with the addition of Good Quality Fill where suitable permeable soils are not present. All on-site sewage disposal systems shall meet the required minimum setbacks provided in Appendix C. Section 18 Sewage Disposal Systems Regulations The on-site disposal fields discussed in this section which can be selected by a Site Assessor, a Septic Contractor/Site Assessor and an Engineer are: • Multiple Trench • Alternative Multiple Trench • Gravelless Disposal Systems • Contour Trench C1, Raised C1, C2 & C3 The on-site disposal field shall not be located: • where, at any time, the maximum water table is less than 0.6 m (2 ft) below the ground surface • in soil which does not meet the definition of permeable soil; • in any area which may be subject to flooding either by a natural body of water or by surface water runoff; • under a roadway; • under a paved area; • under an area used by motor vehicles; • under an area used intensively by livestock; • less than 6.1 m (20 ft) from a foundation; • less than 3.0 m (10 ft) from a parcel boundary or an embankment; • less than 15.2 m (50 ft) from any well; or • Less than 15.2 m (50 ft) from a natural boundary of a body of water. See Appendix C, Table C1 for more details. 1.10.2 Disposal Field Sizing Disposal field sizing not listed in the tables outlined in Appendix D shall be determined using the following formula and calculations: Drainage pipe length (m) = Q (L/d) x SLR (m2 /1000L/d) / 1000 CA (m2/m) 1) Calculate the wastewater flow (Q) 2) Calculate septic tank volume (size) 3) Calculate the length of the disposal field system according to the following: 1) Choose the soil loading rate (SLR) i) For Category I & Category III (permeable soil 2-4 feet) conditions choose: - 36 m2/1000L/day for multiple trench disposal field - 36 m2/1000L/day for leaching chamber disposal field - 31 m2/1000L/day for contour trench disposal field ii) For Category II, Category III (permeable soil 1-2 feet) & Category IV conditions choose: - 41 m2/1000L/day for multiple trench disposal field - 41 m2/1000L/day for leaching chamber disposal field - 36 m2/1000L/day for contour trench disposal field 2) Choose the contact area / linear foot of trench (CA) i) For multiple trench system the CA is 0.6 (m2/m) Page 32 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 ii) For a leaching chamber system the CA is 1.2 (m2/m) iii) For a contour trench disposal field the CA is - for a 0.9 m wide trench is 1.1 (m2/m) - for a 1.2 m wide trench is 1.4 (m2/m) - for a 1.5 m wide trench is 1.7 (m2/m) - for a 1.8 m wide trench is 2.0 (m2/m) Where: Flow (Q) is the design flow referenced from Appendix B or as determined by actual measured readings; Soil Loading Rate (SLR) is the disposal area required for each one thousand litres per day of wastewater generated and is expressed as square metres per 1,000 litres per day (m2/1000L/day); Contact Area (CA) is the minimum square metres per linear metre of gravel/soil interface on the bottom of the trenches in the disposal field. The contact area is expressed as square metres per linear metre (m2/m). 1.10.3 Multiple Trench A multiple trench system has been the conventional method of treating and disposing of effluent. It consists of a series of disposal trenches oriented along the contour connected by a level solid header pipe and footer pipe. In Figure 1.9, a solid header and a perforated (optional) footer pipe are joined by a number of perforated laterals. The trenches should be oriented with the greatest dimension across the slope of the lot. The header pipe and footer pipes are laid level in an attempt to ensure equal flow distribution to the laterals. The width of the trench is a minimum of 600 mm. Wider trenches can be used where required. Lateral trenches shall be installed 2.0 metres apart centre to centre, where site conditions allow. Trenches can be closer together if special care is taken to ensure excavated material from one trench does not fall into the next trench. A minimum 1.5 metre separation distance, centre to centre is required for all disposal fields, however, at all times a minimum of 900 mm is maintained between the trench walls.. Selection of a Multiple Trench Once it has been determined that conditions allow the installation of a multiple trench type system, the minimum total length of trench can be selected from the table in Appendix D. The dimensions of a multiple trench system may be selected as follows: 1. Determine the average daily flow in L/day from the tables in Appendix B. 2. From the test pit information determine soil type, depth of permeable soil and total soil depth to bedrock or water table. 3. From the tables found in Appendix D, determine if soil depths allow the selection of a trench type field and if so determine the depth of trench allowed. 4. If conditions allow the selection of a trench type system, select the length of trenches for the soil type from the tables in Appendix D. 5. Refer to Figure 1.9 for typical layout of a multiple trench system. c t Current to: March 30, 2024 Page 33 Section 18 Sewage Disposal Systems Regulations Layout of a Multiple Trench To use a multiple trench type disposal field the following conditions must be met: 1. There is at least 600 mm permeable soil on the lot for a Category I disposal field size (Appendix D). 2. There is at least 300 mm permeable soil on the lot for a Category II disposal field size (Appendix D). 3. There is at least 300 mm permeable soil on the lot for a Category III shallow bedrock disposal field size (Appendix D). 4. There is at least 1200 mm of Good Quality Fill (GQF) on a lot for Category IV disposal field size, where there is less than 300mm permeable soil (Appendix D). Also, a 3 meter buffer must be maintained around the perimeter of the field bed. 5. There is at least 300 mm permeable soil under the disposal trench. 6. There is at least 600 mm separation between the bottom of the trench and the maximum water table elevation, bedrock or soil with unacceptably high permeability. Where these conditions cannot be met, the selection of another type of disposal field may be required. Page 34 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Figure 1.9 Multiple Trench 1.10.4 Alternative Multiple Trench An alternative multiple trench consists of a series of disposal trenches oriented perpendicular to the contour of the land connected by a level solid header pipe and footer pipe in Figure 1.10. A solid header and a perforated footer pipe (optional) are joined by a number of perforated laterals. The minimum width of the trenches will be 600 mm. Laterals to be installed a minimum of 4 m apart where pipe conditions allow. Selection of an Alternative Multiple Trench c t Current to: March 30, 2024 Page 35 Section 18 Sewage Disposal Systems Regulations To use an alternative multiple trench type disposal field, the following conditions must be met: 1. Determine the average daily flow in L/day from the tables in Appendix B. 2. From the test pit information determine soil type, depth of permeable soil and total soil depth to bedrock or water table. 3. From the tables found in Appendix D, determine if soil depths allow the selection of a trench type field and if so determine the depth of trench allowed. 4. If conditions allow the selection of a trench type system, select the length of trenches for the soil type from the tables in Appendix D. 5. Refer to 6. Figure 1.10 for typical layout of an alternative multiple trench system. Layout of an Alternative Multiple Trench To use an alternative multiple trench type disposal field the following conditions must be met: 1. There is at least 600 mm permeable soil on the lot for a Category I disposal field size (Appendix D). 2. There is at least 300 mm permeable soil on the lot for a Category II disposal field size (Appendix D). 3. There is at least 300 mm permeable soil on the lot for a Category III shallow bedrock disposal field size (Appendix D). 4. There is at least 1200 mm of Good Quality Fill (GQF) on a lot for Category IV disposal field size, where there is less than 300mm permeable soil (Appendix D). Also, a 3 meter buffer must be maintained around the perimeter of the field bed. 5. There is at least 300 mm permeable soil under the disposal trench. 6. There is at least 600 mm separation between the bottom of the trench and the maximum water table elevation, bedrock or soil with unacceptably high permeability. 1.10.5 Gravelless Disposal Systems Gravelless disposal systems offer alternatives to traditional pipe and gravel distribution systems. The use of gravelless systems technology can be advantageous in areas where gravel is difficult to place or may not be readily available. Systems such as chambers and other synthetic aggregate systems must meet appropriate standards for sewage disposal systems distribution and must meet specifications outlined in this Appendix. Gravelless systems may consist of open-bottomed chambers, fabric-wrapped pipe, and pipe wrapped in synthetic materials such as expanded polystyrene (EPS) foam chips. A number of proprietary gravelless systems have been approved for use in specific jurisdictions throughout North America, including Prince Edward Island. Page 36 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Figure 1.9a EZflow System (Multiple Trench) Gravelless technologies, like the leaching chamber system, shall be selected and laid out according to these standards and the manufacturer’s installation recommendations must be approved for distribution by the Minister. Where applicable, system sizing for these systems has been adjusted and approved by the Minister, allowing for increased contact area in these systems. In the leaching chambers systems up to 50% reduction is permitted. With the EZ flow system a reduction of up to 33% is permitted. The EZ flow system (Figure 1.9a) is only permitted for use in a multiple trench design. A typical design layout of a gravelless system like the leaching chamber system have been approved for use in PEI since 1996 and two options for installation approved by the Minister include a Shallow In-ground System and an At-grade System (see Figure 1.11). The in-ground system is used when the following conditions can be maintained: 1. System can be placed within 600 mm of surface; 2. Depth of permeable soil below the system is minimum 300 mm; 3. 600 mm separation to groundwater, bedrock, or “too permeable” soil. 4. Appendix D provides the lengths required for the various lot categories. The at-grade system is used when the conditions required for the in-ground system cannot be met. The at-grade system is required to be backfilled with Good Quality Fill (GQF). The at-grade system is used when the following conditions can be maintained: c t Current to: March 30, 2024 Page 37 Section 18 Sewage Disposal Systems Regulations 1. System is placed at grade; 2. Depth of permeable soil below the system is minimum 300 mm; 3. Soil under the system is scarified; 4. 600 mm separation to groundwater, bedrock, or “too permeable” soil. 5. Appendix D provides the lengths required for the various lot categories. Layout of Chamber System (Multiple Trench) The trenches shall be excavated parallel to the ground contour. The lines of the chambers shall be of equal length. A minimum depth of 300 mm of permeable soil below the bottom of any trench of the disposal field is required. The minimum distance of the walls of adjacent trenches shall be 900 mm and the minimum spacing between the chambers shall be 1800 mm centre to centre. The bottom of each trench shall be level and of equal elevation. Each line of chambers shall be fed from a header via tees and the downstream end of each line shall be connected to a bottom header. For gravity fed systems, the inlet pipe shall extend through the end plate and terminate on an adequate splash plate (concrete patio stone) or an energy dissipation device. This is required for both high and low pressure distribution systems. Where the total length of leaching chambers in a multiple trench configuration exceeds 150 m, they shall be constructed in two or more separate disposal fields connected to the septic tank by using, a) a sewage pumping station or b) a siphon chamber. Figure 1.10 Alternative Multiple Trench Page 38 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Layout of EZ Flow System (Multiple Trench) For use in raised bed applications, the EZflow 1202 is a bundle of 2 pieces each of 300mm in diameter by 3.0 meters long. The EZflow 1202 is designed for use in trench applications. Installation Instructions The instructions for installation of EZflow products are given below. In cases where linear footage required is not in multiples of 10, installer may (a) reduce the product to needed length and refasten netting to the pipe or, (b) use an additional 10 feet of product to exceed the required trench length. Disposal Field Use The EZflow 1202H, systems can be used in disposal fields as follows: 1. The EZflow1202H system is to be installed side by side, in a 600 mm wide trench, one cylindrical bundle shall be of solid aggregate fill (without pipe) and the other cylindrical bundle (with pipe) shall be of aggregate and drainage tile. 2. Disposal field trenches shall follow the ground surface contours so that variations in trench depth will be minimized. 3. The minimum clearance distances required shall be met. Determine the permitted location and excavate the trenches. 4. Construction of trenches shall comply with these Standards. Trench wall and bottom are to be raked or scarified to loosen soil. 5. Remove plastic EZflow stretch wrap prior to placing bundles in the trench(s). Remove any stretch wrap in the trench before system is covered. 6. Place first EZflow bundle(s) in the trench. The next bundle(s) with pipe are joined end to end with approved internal pipe couplings. Connect and place additional EPS bundles with pipe in trenches until the required linear footage has been obtained and cap the ends with approved caps. 7. If installing an EZflow product that does not contain a pre-inserted geotextile, then a geotextile barrier cover shall be placed over the top of these products prior to backfilling. The barrier material must meet the requirements of these Standards. 8. These products shall be covered with a minimum of 300 - 400 mm of backfill. 9. The trench top shall be shaped or mounded to ensure surface water runoff. Where the total length of the field bed in a multiple trench configuration exceeds 150 m, the field bed shall be constructed in two or more separate disposal fields connected to the septic tank by using, a) a sewage pumping station or b) a siphon chamber. The design layout of an EZflow system is similar to a standard multiple trench system as shown in Figure 1.9a. c t Current to: March 30, 2024 Page 39 Section 18 Sewage Disposal Systems Regulations Page 40 Current to: March 30, 2024 t c Figure 1.11 Chamber Systems 1.10.6 Contour Trench C1 and Raised C1 A contour trench is a conventional disposal field constructed along the contour line. Details of a C1 contour trench are shown in Error! Reference source not found.. A C1 trench may be used: • where the surface slope at the location of the trench is at least 5 per cent • where the width of the lot will allow for the length of the selected C1 trench Sewage Disposal Systems Regulations Section 18 A C1 trench is fed by a gravity distribution system, except where a pressure system is required where the distribution field is at a higher elevation than the septic tank. An interceptor trench or swale may be necessary, to intercept and divert surface or ground water if a perched water table exists, or if the system is located at the lower end of a long slope. Refer to Section 1.6 for more information on interceptor trench or swale. Depth Limitations for a C1 Contour Trench Figures 1.12 and 1.13 illustrate two possible C1 contour installations. It is important that the C1 trench excavation does not penetrate the soils with unacceptably low permeability and that there is a minimum of 300 mm of permeable soil under the disposal field. It should also be noted that the draining of a perched water table may allow for the increase of an effective soil depth. As illustrated in the raised C1 cross section ( Figure 1.11), clearance to water table, bedrock and soils with unacceptably high permeability can be increased if the trench is raised by not more than 300 mm. This trench will require an earth cover as illustrated and an interceptor trench and/or swale. Selecting a C1 Contour Trench The length of a C1 trench is determined using the table in Appendix D. The table used will depend on the average daily flow leaving the dwelling and the depth of permeable soil. Other factors include the amount of room for a contour system on the property and the total depth of soil above water table, bedrock, or soil of high permeability. The length of a C1 trench will range between 30 m and 60 m. If a C1 system cannot be selected due to limiting soil conditions, then a C2 or C3 system may be considered with the addition of Good Quality Fill (GQF). Criteria for selecting a C1 system: a) Determine the number of bedrooms and low flow fixture option. b) Determine the surface slope at the proposed location of the disposal field. If the slope is less than 5 per cent or greater than 30 per cent, a C1 system cannot be used. c t Current to: March 30, 2024 Page 41 Section 18 Sewage Disposal Systems Regulations Figure 1.12 Contour System C1 c) Determine the category of the soils in the area of proposed disposal field. If the total depth of permeable soil is less than 600 mm a C1 system cannot be used. d) Determine the maximum depth to water table, bedrock, soil with unacceptably high permeability. If this value is less than 1.2 m, then a C1 system cannot be used. e) Determine the lot category. f) Once the lot category, number of bedrooms and system type are determined, refer to Appendix D to determine the trench length and width. g) The cross section dimensions of the disposal field shall be those shown in Figures 1.12 and 1.13 Layout of a C1 Trench Figures 1.12 and 1.13 illustrated the layouts of fully trenched C1 and raised C1 trenches. A trench is excavated along the contour to the required width and depth. The trench bottom is perfectly level throughout its length and width. The bottom of the trench and the down slope side walls are then raked. After raking, filter sand is deposited in the bottom of the trench to a depth of 75 mm, with excess filter sand raked to the down slope side of the trench. The sand is placed as shown in Figure 1.12 Page 42 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 & 1.13. Once the sand is in place a minimum of 100 mm of gravel will be placed. The amount of crushed rock at the tee will exceed 100 mm because the pipe will be sloped toward the end of the system. 1.10.7 Contour Trench C2 A C2 contour trench may provide an alternative in situations where a C1 trench cannot be used. Figure 1.12 illustrates the layout of a standard C2 trench. A C2 trench is similar to a C1 trench in that effluent leaving the trench is expected to move laterally in the soil below the organic surface layer. In a standard C2 contour trench a layer of Good Quality Fill, above the ground surface, enables saturation of the existing soil to the natural ground surface preventing possible breakout. Use of C2 systems is limited to locations where the surface slope at the location of the trench is at least 5 per cent. If the slope is less than 5 per cent, a multiple trench or chamber system must be used. The exact selection is dependent on the site. A modified C3 trench, constructed according to Figure 1.14, should be used instead of a C2 trench where uneven surfaced lots or boulder fields are encountered. A C2 trench is fed by a gravity distribution system, except that a pressure system is required where: • the length from the tee feeding the system, to the end of the distribution pipe, exceeds 23 m • the natural slope is not constant and a gravity system may tend to concentrate effluent in one part of the system • The distribution pipe is at a higher elevation than the septic tank. Where groundwater, bedrock, or soil with unacceptably high permeability occurs under a C2 trench, a 600-mm vertical separation must be maintained between the bottom of the disposal field trench and the above conditions. This may require the use of a C3, rather than a standard C2, to ensure that this 600 mm separation is met. c t Current to: March 30, 2024 Page 43 Section 18 Sewage Disposal Systems Regulations Page 44 Current to: March 30, 2024 t c Figure 1.11 Contour System Raised C1 Selection of a C2 Trench The length of a C2 trench is determined using the table in Appendix D. The table used will depend on the average daily flow leaving the dwelling and the depth of permeable soil. The amount of area for a contour system on the property, and the total depth of soil above water table, bedrock, or soil of unacceptably high permeability must be taken into consideration. The length of a C2 trench will range between 30 m and 60 m. If a C2 system cannot be selected due to limiting soil conditions, then a C3 trench system may be considered. Sewage Disposal Systems Regulations Section 18 Criteria for selecting a C2 system: a. Determine the number of bedrooms and low flow fixture option. b. Determine the surface slope at the proposed location of the disposal field. If the slope is less than 5 per cent or greater than 30 per cent, a C2 contour trench cannot be used. c. Determine the depth(s) of permeable soil. If the total depth of permeable soil is less than 300 mm a C2 system cannot be used. d. Determine the depth to water table, bedrock or soil with unacceptably high permeability. If this value is less than 1.2 m, then a C2 system cannot be used. e. Determine the category of lot. f. Once the lot category, number of bedrooms and system type are determined, refer to Appendix D to determine the trench width and length. The cross section dimensions of the disposal field shall be those shown in Figure 1.12. Layout of Standard C2 Trench Figure 1.12 illustrates the layout of a standard C2 trench. The toe of the trench is excavated along the contour to a depth of 175 mm into the permeable soil. The trench is then excavated to the necessary width while keeping the bottom of the trench perfectly level throughout its length and width. The trench bottom and down slope side walls are raked. The depth of the trench from the upslope side will be greater than the depth at the toe. A 75 mm layer of filter sand is deposited in the bottom of the trench and excess filter sand is raked to the down slope side of the trench. A minimum 125 mm depth of crushed rock is placed on top of the filter sand. This will ensure that the distribution pipe is raised so that its invert is at or above the ground elevation at the down slope lip of the trench. The amount of crushed rock at the tee will exceed 125 mm because the pipe will be sloped toward the end of the trench. c t Current to: March 30, 2024 Page 45 Section 18 Sewage Disposal Systems Regulations Page 46 Current to: March 30, 2024 t c Figure 1.12 Contour System C2 1.10.8 Contour Trench C3 A C3 trench is shown in Figure 1.13. This trench consists of a distribution pipe and rock filled trench constructed entirely in good quality fill. The Good Quality Fill (GQF) and trench must follow the site contour. • additional depth of good quality fill is required to protect groundwater • site conditionsCuneven sites including boulder fields, or undulating wooded areasCrequire a modified C3 system, Figure 1.14, instead of a C2 trench • the surface slope is at least 5% Effluent leaving the trench in a C3 is expected to move vertically through the Good Quality Fill (GQF) until it reaches the natural soil under the fill. Effluent will then move vertically into the natural soil if the permeability allows, or down slope through the good quality fill where the permeability of the natural material is inadequate to allow the effluent to enter the soil. Sewage Disposal Systems Regulations Section 18 Selection of a C3 Trench Where ground water, rock or soil with unacceptably high permeability occur under the C3 trench, the depth of good quality fill must be enough to provide a 600 mm vertical separation between the bottom of the distribution trench and the ground water, rock or soil with unacceptably high permeability. Under these conditions, select a C3 as shown in Figure 1.13 with a depth of good quality fill adequate to give the 600 mm separation, but not less than 600 mm. The dimensions of a C3 system can be determined as follows: a. Determine the number of bedrooms and low flow fixture option. b. Determine the ground surface slope at the location of the trench and confirm that is greater than 5% and less than 30%. c. Based on the flow determined in (a) and the slope determined in (b), the length of the C3 and the type of good quality fill required is selected from Appendix D. d. If the distance from the bottom of the trench to ground water, bedrock, or soil with unacceptably high permeability is a factor, select the depth of good quality fill required to give the minimum 1 m separation. Where separation to ground water, bedrock, or soil with unacceptably high permeability is not a concern select a depth of 600 mm good quality fill under the trench. e. Select other dimensions of the system from Figures 1.15 and 1.16. Where a C3 type system is installed on a lot with very little permeable soil over solid bedrock or soil with unacceptably low permeability and effluent is expected to be obvious at the down slope toe of the sand buffer it is recommended that a 150 mm layer of sand plus final cover material and sod be extended beyond the buffer. The down slope width of this extra buffer is determined on a site by site basis but should extend at least 7 m or to the point where there is adequate permeable soil or root zone to absorb the effluent. Layout of a C3 Trench The required dimensions of the buffers for a C3 trench are shown on Figures 1.15 and 1.16. Fill used for the buffer upslope of the trench may be Good Quality Fill or clean fill material. Good Quality Fill is required for down slope and end buffers. The down slope edge of the rock trench in the C3 is laid out to follow the contour of the site. c t Current to: March 30, 2024 Page 47 Section 18 Sewage Disposal Systems Regulations Figure 1.13 Contour System C3 Page 48 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Figure 1.14 Modified C3 for Uneven Surface Lot 1.11 Gravelless Disposal System Gravelless disposal systems offer alternatives to traditional pipe and gravel distribution systems and the Minister will consider the approval of alternate gravelless technology if proponents submit the following information: - Soil effluent loading and hydraulic loading rates; - Equivalent void space (to crushed rock); - Capability of the system to withstand pressure of backfill and extraneous loads; - Manufacturer’s installation instructions; c t Current to: March 30, 2024 Page 49 Section 18 Sewage Disposal Systems Regulations - Documentation of approval in other jurisdictions; - Applicability to Prince Edward Island; - Benefits to Prince Edward Island. 1.12 Requirements for Good Quality Fill (GQF) 1.12.1 Site Preparation Prior to the installation of an on-site sewage disposal system (septic), a site suitability assessment shall be completed to verify the site conditions. This assessment should take place in the proposed area of the disposal field or at least within a 75 foot radius of the proposed location of the disposal field. The assessment shall provide details with respect to the depth to bedrock, water table, and the depth of permeable soil as outlined. Once this assessment has been completed, the disposal field can be selected to suit the lot and development. A critical piece of information during the selection of the disposal field is to determine if and how much fill material may be added to the disposal field area in order to accommodate the design of the system. As the system is only as good as the natural soil on-site and the fill added, it is very important not only to perform an assessment of the natural soils but also the fill material that is to be added to the disposal field area. This material is called Good Quality Fill (GQF). 1.12.2 Specifications Typically, in PEI the GQF added to the site is a reasonably uniform sand or sandy gravel with a small portion of silt/clay. The recommended sieve specifications for suitable sand are given in Table 1.4 and should be used for all systems that require fill material under and around the disposal field and in the buffer areas of the disposal field. The recommended Good Quality Fill Specifications are listed in Table 1.4. Contractors should strive to meet or exceed these recommendations. However, sieve analysis results can vary due to sampling. For this reason, the Minister will accept up to 15% silt & clay passing at the No. 200 sieve. Table 1.4 – Good Quality Fill (GQF) Effective Particle Sieve Percent Passing by weight (%) Size (mm) 1 in 25 95 to 100 3/8 in 9.5 70 to 100 No. 200 0.075 2.5 to 10 1.12.3 Contractor’s Responsibility The Septic Contractor has the ultimate obligation to ensure that the disposal field is installed in material that is suitable and meet the requirements of these standards even though the material may be purchased and installed by another Fill Contractor. It is recommended that the Septic Contractor inform the Fill Contractor clearly of the fill requirements. Page 50 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 1.13 Buffers The down slope side of the contour trench may need to be extended due to limited permeable soils on site. If desired, a 150 mm layer of Good Quality Fill (GQF) could be extended 5 meter down slope of the standard 5.9 meter buffer. APPENDIX B Flow Tables 1. The individual on-site sewage disposal system shall be designed and constructed to adequately treat and dispose of the expected maximum flow of sewage. 2. The disposal system must be designed to receive all sewage from the building or structure except cooling water, roof, foundation or surface drains or backwash from water treatment devices, unless otherwise approved by the Minister. Backwash from water treatment devices add an extra hydraulic load and may create additional concerns depending on the specific treatment technology. Discharge of this backwash to an on-site sewage disposal system is only recommended if the system has been specifically designed by an engineer to accept the specific discharge. 3. The minimum design sewage flow from any residential structure or dwelling, shall be 900 L/day. When it is anticipated that the sewage flows from the dwelling or structure will exceed the 900 L/day minimum, it is recommended that the sewage flows, as indicated in the following Table B1, be utilized: Table B1 Residential Flows W/Standard Water Closets Low Flow Water Closets Number of Bedrooms (Litres) (Litres) 2 bedrooms or less 900 720 3 bedrooms 1,400 1,100 4 bedrooms 1,900 1,500 Each additional bedroom 450 350 (For residential applications where 6 litre toilets are installed, a 20 percent reduction in design flow may be applied). 4. The minimum design sewage flow from any multi unit residential structure or dwelling such as, apartments, condominiums, cottages, hotels, etc., shall be 900 L/day. When it is anticipated that the sewage flows from the dwelling or structure will exceed the 900 L/day minimum, it is recommended that the sewage flows as indicated in the following Table B2 be utilized: Table B2 Multi Unit Residential Flows Average Daily Flow (L/Day) Unit Type Standard Water Closets Low Flow Water Closets For each 1 bedroom unit 900 720 For each additional 1 bedroom unit 450 350 For each 2 bedroom unit 900 720 For each 3 bedroom unit 1,400 1,100 For each 4 bedroom unit 1,900 1,500 c t Current to: March 30, 2024 Page 51 Section 18 Sewage Disposal Systems Regulations 5. Industrial wastewater shall not be discharged into on-site sewage disposal systems designed for sanitary sewage disposal unless prior approval is obtained from the Minister. Special designs or pre-treatment may be required for industrial waste-water. 6. All restaurants or other establishments involved in food preparation activities shall install external grease tanks. 7. The design sewage flows from other residential, commercial, industrial and institutional buildings or structures should be based on the design wastewater flows prescribed in Table B3 of this appendix. The minimum design flow from other residential, commercial, industrial and institutional buildings or structures shall be 900 L/day. The designer for these types of systems may want to consider the characteristics of the waste water in the process of design. 8. Where actual metered flow data indicating maximum daily flows are available, such flow data may be substituted for the sewage flows listed in this appendix, under the following conditions:
Part document.segment-3
Sewage Disposal Systems Regulations — segment 3
- document.segment-3 Verify source ↗
Sewage Disposal Systems Regulations — segment 3
This provision sets minimum and table-based design wastewater flows, requires supporting flow data when submitted, and lets the Minister reduce flows or decide disputed flow rates.
• The minimum design flow for residential, commercial, industrial and institutional buildings or structures is 900 L/day. • They should cover the most recent two (2) week peak period of operation. • A 20 to 50 per cent increase factor should be used in the design flow to accommodate potential future flow increases, occasional peaks, etc. • Flow meter data, from the facility shall be submitted by the Engineer or site assessor at time of submission, also include information regarding actual occupancy or production volume when unit flows are calculated. 9. A reduction in the design flows may be allowed by the Minister when permanent low-volume devices are to be installed in the proposed building or structure. 10. Design flows in this Appendix B are recommended minimal design flows and if evidence of larger flows exist or are expected, the larger flows should be used. In many cases the tables provide several flow rates for the same/similar activity (examples: church halls, restaurants, etc) and the system designer must decide which of the flows provided in the tables is most representative for the specific design. If there is a question related to which flow rate is most appropriate, the Minister will have the final decision. Table B3 Design Wastewater Flows Maximum Design Flow Facility Unit of Measure (Litres/day) Institutional Assembly Hall/Churches: With kitchen Seat 45 Assembly Hall/Churches: No kitchen Seat 23 Fire station without full time employee, Person 19 floor drains or food Page 52 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Table B3 Design Wastewater Flows Maximum Design Flow Facility Unit of Measure (Litres/day) Town Hall Seat 23 Medical/Personal Care Hospital: Including laundry Bed 1,050 Nursing/Special Care Home Resident 600 Nursing/Special Care Home: Add per Employee 80 employee Medical Office: Doctors, nurses, medical Person 273 staff Medical Office: Office staff add Person 80 Medical Office: Patient add Person 23 Dental Office Chair 757 Dental Office – waterless units Chair 0 Dental Office: Staff/Patient add Person 80 Schools 90 School: Cafeteria, gym and shower Student Add to base flow for school School: Cafeteria only Student 80 Add to base flow for school School: Gym with showers only Student 30 Add to base flow for school School: Elementary – washrooms only Student 26 School: High – washrooms only Student 45 School: Junior high – washrooms only Student 34 School Boarding: Resident student Student 136 School Boarding: Non-resident staff Person 80 Food Service Bakery: Sanitary only Employee 68 Bar/Lounge Seat 140 c t Current to: March 30, 2024 Page 53 Section 18 Sewage Disposal Systems Regulations Table B3 Design Wastewater Flows Maximum Design Flow Facility Unit of Measure (Litres/day) Bar/Lounge: Add per employee Employee 80 Restaurant: Not 24 hour Seat 160 Restaurant: Add per employee Employee 80 Restaurant: Take Out Seat 70 Taverns/Bars/Lounges with minimal food Seat 140 service Commercial Office Employee 80 Beauty Salon Station 400 Beauty Salon: Add for personnel Person 38 Veterinary Clinic (3 doctors or less): No Total 2,900 boarding Dog Kennel Enclosure 73 Laundromat: Self Serve Machine 1,700 Laundromat: In apartment building Machine 1,700 Shopping Centre Space 10 Shopping Centre Employee 80 Commercial/Automobile 570 Automobile Gas Station: Single hose pump Unit (does not include restaurant) Car Wash * Vehicle 189 * requires oil water separators with discharge to a closed storm sewer or an in-ground disposal system. Commercial/Hospitality Motel Unit 320 Motel Housekeeping unit 450 Motel: Dining room Seat 160 Motel: Bar and lounge Seat 68 Hotel Guest 136 Hotel: Add for employees Employee 36 Page 54 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 Table B3 Design Wastewater Flows Maximum Design Flow Facility Unit of Measure (Litres/day) Boarding House/Dormitory Resident 180 Senior Citizens Home Resident 227 Day Care Centers: Staff and children Person 80 Recreation/Camping Campgrounds: Tents only – No service Site 320 Campgrounds: Trailers - water and Site 320 electrical – 2 way Campgrounds: Trailers - water, sewer and Site 390 electrical – 3 way Campgrounds: With central comfort Add for dump 390 station stations Day Camps: No meal Person 70 Day Camps: Meals Person 100 Summer Camps Camper/Instructor 160 Parks, Beaches and Picnic Grounds Picnic and Fairgrounds: With bath houses, Person 38 showers, toilets Picnic and Fairgrounds: With toilets only Person 18 Beaches with Showers and Toilets Person 40 Visitor Centre Person 18 Visitor Centre: add Employee Employee 80 Golf/Country Clubs Golf/Country Club Round 18 Golf Clubs and Restaurant add Seat 35 Golf Clubs Fixture 1,800 Golf/Country Clubs: Showers Person 40 Golf/Country Clubs: Day staff – Add Employee 80 c t Current to: March 30, 2024 Page 55 Section 18 Sewage Disposal Systems Regulations Recreation General Theatre Seat 18 Theatre: Drive-in – food Space 23 Recreation/Sport Bowling Alleys: Without bar and restaurant Alley 105 Bowling Alleys: With bar or restaurant Alley 800 Ice Rink Seat 11 Ice Rink: Participant add Person 38 Stadium Seat 18 Swimming Pool Customer 45 Water Slide Park Visitor 18 Gym: Participant Person 38 Gym: Spectator Person 18 Tennis/Racquetball: Excluding food Court 946 Outdoor Sport Facilities: Toilet only Person 18 NOTES: Approximate Flushing Frequencies Residential 5 flushes per day Schools 2 flushes per student per day Hotel/Motel Room 4-6 flushes per day Restaurant 0.5 flushes per meal per day General Commercial 2-4 flushes per employee per 8 hr Industrial 3 flushes per employee per 8 hr Ski Areas 1 flush per skier per day Campgrounds with Facilities 3 flushes per person per night Note: Flow reduction - Facilities that install low flow or no flow fixtures may have reduction of flow applied. Site assessor or consulting engineers may apply 20% to 50% reduction to the design based on design approach. Page 56 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 APPENDIX C Table C1 – Minimum Setback Distances c t Current to: March 30, 2024 Page 57 Section 18 Sewage Disposal Systems Regulations Appendix D Disposal Field Length Selection Tables Minimum Field Tile Length by Lot Category Page 58 Current to: March 30, 2024 t c Sewage Disposal Systems Regulations Section 18 c t Current to: March 30, 2024 Page 59 Section 18 Sewage Disposal Systems Regulations (EC504/21; 281/24) Page 60 Current to: March 30, 2024 t c
Provision text is displayed from LexChat’s stored statute record. Use the official source links to verify amendments, commencement, and current legal force.
Ask AI about this statute
Sewage Disposal Systems Regulations
Sign in to ask AI about this statute
Sign in to start authenticated, citation-grounded statute research.
Sign inLexChat organizes source-backed legal information for research. Verify amendments, commencement, and current legal force with the official publisher before relying on it.